Archive

Archive for the ‘Tip of the Day’ Category

Electrical Tip of the Day: Testing wires for lightning damage – MegOhm test

July 22nd, 2010 artisanchris No comments

Here in the Lafayette area it is summer storm season, and it has been a very bad year for high yield lightning strikes.  We have a number of jobs going on right now where we are working with clients to get damaged wiring in homes replaced.

The question that always comes up is:  “How do I know if there has been damage, is there a way to test the wires in the walls?”.  Thankfully, the answer is YES.  We do in fact have a way to test for this.  Its called an insulation resistance test, also know as a MegOhm test or sometimes referred to in the trades as “Megging”.

megger

The theory is simple really – the electrical resistance of the insulation on a conductor or in a piece of equipment can be tested and measured by isolating the conductor from ground, applying a high voltage over time, then measuring the results.  In most residential situations we use a 300 to 500 volt DC test over 10 minutes.  When done with care and by knowledgeable electricians it is a very reliable test.

So – here is the process for preforming a megohm test in a home:

1) ALL electrical current to the dwelling must be shut off

2) All appliances, light fixtures, heating and cooling equipment, dimmers, GFCI’s, AFCI’s, low voltage systems and any “plugged in” or “hard wired” equipment must be disconnected from the circuit(s) to be tested

3) The best practice at this point is to then isolate each individual wire – taking apart every splice, junction, and connection in the circuit to be tested

4) Next, the testing of the insulation can be preformed – this part actually goes pretty quick

5) After testing any conductor that fails to meet the testing standards should be considered damaged and marked for replacement

So, now a word of caution is in order.  If you have had a major strike and the  electrician, general contractor (or restoration company) helping you out with the repairs has not told you about this process, then GET ANOTHER COMPANY.  MegOhm testing is really the only way to know if damage has occurred, and even then it is not a fool proof testing process. You can’t be sure by visible inspection alone, and you can’t visibly inspect most of the wires in a home.  Lightning is crazy stuff, it has a super high voltage and travels very fast.  If your home has been hit tell your insurance agent you want it tested!  We also HIGHLY RECOMMEND that any home that has had a strike install Arch-Fault breakers on all the branch circuit wiring, as well as make sure proper fire alarms are in place (and a quality A-B-B fire extinguisher is located on each floor).

Here are some pictures of lighting damage from a few projects we have going on now

photophoto (2)photo (3)photo (4)photo (5)

Categories: Tip of the Day Tags:

Electrical Tip of the Day – Data / Voice / HDTV / Satellite TV cabling – we can help!

July 8th, 2010 artisanchris No comments

In this day and age of cutbacks, start up companies, “magic jacks”, new technology from TV, internet, and telephone providers; and the mentality of many of these companies to make the fast buck it can be hard to know were to turn to manage issues related to these services.  Specifically the cable infrastructure and trouble shooting.

electrician_lafayette_monticello

Artisan Electric is qualified  to do all forms of networking cabling – including:

  • Category cabling for home data networks and structured wiring
  • Coaxial video cabling for Internet /HDTV /satellite / home automation/ audio projects
  • Telephone cabling for voice and DSL
  • Audio and whole house sound
  • All forms of low voltage wiring for home automation and lighting control
  • Home and office fiber optic cabling  installation /terminations
  • Certified testing for structured wiring networks

If you are having trouble with service providers getting you the results you want (or expect) let us know – we can help.  In most cases we can do a better job for less money and avoid the “staple it to you house and drill a hole in the wall” install method!

Here is another good (FREE) resource for testing Internet speeds, the  SPEAK EASY SPEED TEST .  Truthfully many providers have a bad habit of selling you upload / download speeds that they are not actually providing.  If you can test it and you are not getting what you are paying for then there is a good argument to be made with your service provider for improved service or a discounted rate.

Categories: Tip of the Day Tags:

Electrical Tip of the Day: 10 Ways to save money on your electric bill

July 2nd, 2010 artisanchris No comments

This is a great article we thought we would pass along – re-posted with permission from our friends at Change of Address.Org

10 Ways to Save Money On Electricity Bills

It’s that time of year again and as our central air conditioning units work overtime to cool our houses this Summer, our electricity bills start to skyrocket.  It’s not uncommon for a power bill to double through the Summer months and given the heat there is only so much we can do about it.  In a few States with deregulated electricity like Texas you can shop around for lower electricity rates (priced in kilowatts/hour).  If that’s not an option for you (or even if it is) you can still save a bundle on your electricity bills by following these 10 Ways To Save Money On Electricity Bills.

  1. This one is one you hear a lot yet most of us STILL do it.  You should try to not pre-rinse your dishes before putting them into the dishwasher.  Why?  Because you waste hot water and more has to be heated.  This of course applies to people with electric water heaters (you can also buy a gas model to reduce electricity consumption – but then watch your gas bill).
  2. Continuing with dishwashers, you should look into purchasing a new one because the newer generation is so much more energy efficient you can usually pay for the cost of the new dishwasher within one year due to decreased power consumption.  You can also save by avoiding the use of the heat dry option on your dishwasher.
  3. Surprisingly another great way to save money is to simply turn your ceiling fans off when you are not in the room.  For some odd reason people leave ceiling fans running most of the time and especially in a home with central air this should not be necessary.
  4. Lights, lights, and more lights.  C’mon already shutoff the lights when you are not in the room and you don’t need to use lights as much during the daytime.  This is a major pet peeve of mine and simply wastes electricity needlessly.  You should also consider switching to CFL bulbs to both last longer and reduce the amount of electricity that your lights draw.
  5. TV’s are everywhere!  If your home is like my home there is a TV in just about every room and generally the TV’s are on even if nobody is in the room.  Talk about lazy, we can even use the remotes to shutoff the TV’s when we leave the room.  This is a completely unnecessary use of power.
  6. Computers should also be turned off when not being used.  Why do we leave computers on all the time?  Do we expect that they will magically tweet everything going on in the home (I certainly hope not).  They should at least be using the built-in power saving features to turn off monitors, etc. after a few minutes of being idle.
  7. Washing machines can consume a lot of electricity.  Did you know that front-loading washing machines use 50% of the power and 40% less water than top loading wasters?  That’s a pretty ridiculous savings that again can quickly pay off an upfront investment in a newer washer.
  8. Clothes dryers are another power hungry appliance that you simply need to do basic maintenance on.  Make sure to clean the lint filter between each use.  Building up lint doesn’t only cause the machine to be less efficient it’s also a serious fire hazard.
  9. Refrigerator use needs to also be sensible.  Don’t over-cram food into your refrigerator as it makes it work harder to keep the excess cooled.  Also, don’t put hot food directly into the refrigerator (let it cool first).  You should also avoid putting the refrigerator right next to a heat source (like an oven).  Lastly, of course try to use an energy efficient refrigerator if possible.
  10. Ovens can also pull a lot of juice (microwaves, toaster ovens, and electric stoves).  Did you know that food cooks faster when placed as close as possible to the edge of the rotating tray in a microwave?  The faster it cooks the quicker the microwave is shutoff and not consuming as much power.  Also, try to use a toaster oven over a traditional oven when possible to reduce the amount of electricity used.  Lastly, don’t constantly open up the oven to check on food, use the light that’s what it’s there for (so you can see without letting a bunch of heat out of the oven).

Most of these tips are common sense ways to reduce your power bill and they generally help all year long (not just in the Summer).  We  definitely recommend that you keep power consumption in mind (more frequently than every time you receive your electricity bill).

Categories: Tip of the Day Tags:

Electrical Tip of the Day: Light Fixture Restoration 101

May 20th, 2010 artisanchris No comments

We deal with a lot of historic properties, both on the commercial and residential sides of the business.  On thing that comes up on a regular basis is the question of what to do with those original fixtures when doing updates and remodeling.  In many cases it may be in the best interest of the project to rewire and restore these old fixtures rather then replace them.  Here are a few things for you to consider while making those decisions:

1)  Many historic fixtures can be rewired and grounded to be made as safe as any new fixture you might purchase.  We typically can replace all the wring and lamp sockets in most of these fixtures without changing their appearance.

2)  Replacement reproduction parts, missing glass and “finals”, new shades and trims, and decorative chain can all be fabricated or bought now for these projects.  We even have suppliers who can match and remake the old “slumped” glass panels and faceted hanging “jewels” for fixtures.  We can even costume cut and replace stained glass panels!

3)  To maintain that vintage look we can get new UL listed lamp cord that still has the old tweed cloth covered outer casing – we can even get vintage reproduction cord ends and switches.

4)  On the commercial side of things we can re-build old florescent fixtures / outdoor lanterns / signage lighting / goose necks / and old shop fixtures, using  modern parts and materials to make the efficient and safe.  We can even convert old gas fixtures to electric or refurbish old gas fixtures to be actual working gas lights again!

5)  We typically recommend that the original finish, know as the patina, be left undisturbed on a fixture – particularly if it is of historic value.  However – if we need to take it back down to metal, get it bead blasted and structurally repaired, then stat from scratch with a new powder coat or plating we can do that as well.

Here are some pictures of some fixture projects we have had in the shop – lets us know if there is anything we can help you with!

german light re-fit

peoples brew fixture

new lamp socket - bocker fixturebocker fixture re-wiregas light re-fit

Categories: Tip of the Day Tags:

Electrical Tip of the Day: Ceiling fans save money!

April 15th, 2010 artisanchris No comments

Spring is here… and not too far down the road we will be suffering thru the dog days of summer, and the fight to stay cool and comfortable in our homes.

That brings us back to my old friend the ceiling fan.  I love fans… they are efficient, they are eco-friendly as compared to the manufacturing and use of AC systems, they extend the season you can keep the AC turned OFF, they help with winter heating (by as much as 25% in an old home), and with all the options available today they can add a real statement to a home.

F529-BS-CH.jpg cooler fanSo what do they actually cost to run you ask… here is a quick break down on costs for use of each of these appliance loads, based on a 12 hour run time per day with current average electrical rates.  This in only meant to be a base line – the cost of running Window AC units and Central Air can go up or down form this dramatically based on the age of the equipment, the efficiency of the system.

COST PER DAY TO RUN

Ceiling Fan = ($.10)
Window Air Conditioner = ($1.63)
Central Air System = ($4.30)

 

 

 

Ceiling fans are very efficient – they use about as much power as a 100 watt light bulb to run.  If you have any questions about applications or installations we would be happy to take a look.  We get our fan products thru Kirby Risk – and in most case these better units come with a 5 to 10 year motor life warranty.

Electrical Tip of the Day: Surge protection for your expensive electronics is a must!

April 13th, 2010 artisanchris No comments

Surge protection is the kind of thing that no one wants to think about or spend money on, until the worst happens.  It’s not “cool” and is not the kind of thing thing that comes up in causal conversation at the gym.  “Say Bob, what kind of surge protection you running these days”, just kind of weird ah?

Stay with me here… let’s say its spring time, and you just went out and bought that wall hung 60″ LCD High Definition TV you have been drooling over all winter.  Maybe a little gift to yourself for making it to spring – after all it’s baseball season right?  We both know you got a bundle of money tied up into your new toy; and if you dropped the change on home theater components to go with it you very well may have a months wroth of wages into “your system” – yet some how you have convinced yourself that YOU NEED THIS and that your wife will approve.  It’s OK – we all do it.

With spring also comes squirrels… starving from winter and more then a little wound up.  Still, its cold at night – and that big metal thing behind your house is warm year round, good place to take a nap if your a squirrel. Then it comes… first that unnatural electrical arching sound, then the lights flicker for a few seconds – wait for it, and BA-BOOM!!!  Hours later the power is restored and you find yourself sitting in front of your new TV – head in your hands, crying.  You knew it was smoked as soon as you tried to turn it on.  Yet you keep trying, on, off, on, off, on, off – “come on, you can do it”.  Like any good tech user you head to your computer to look for some answers on Google – surly it is just a fuse or something.  then you realize how bad of a day it is really going to be  – computer is fried too, lost everything on the drive.  UGH!

man-pulling-hair-out-2.jpg

Now your old friend surge protection is looking pretty good :)

Here is a link to a company that makes a full line of products we really like, PANAMAX.  We can assist you with small point of use systems for an entertainment center or computer – all the way up to whole whose or whole office electrical system protection units *TVSS*.

Categories: Tip of the Day Tags:

Electrical Tip of the Day: Ground Fault Circuit Interrupters (GFCI’s) required for pools, spas, hot tubs, and more…

April 8th, 2010 artisanchris No comments

These days we are surrounded by portable spas, inexpensive all-in-the-box inflatable pools, hot tubs, spa garden tubs, steam baths, and any number of new water related play time products.  Electricity and water typically do not play nice together… when you take a vessel, fill it with water, then wire it up with more then enough electrical potential to cook and elephant you have created a uniquely dangerous situation.  In my experience most people take this for granted, and tend to make the assumption of  “it must be safe” or they would not sell it, right?

All of these types of products MUST be  GFCI protected.  The National Electrical Code has complete section of the code book (2008 NEC – Article 680) dedicated to this topic.  Everything from little wading pools to that fancy new pond your thinking about putting in this spring.

I found this CPSC write up on the subject I thought I would share.  In the end, what it comes down is that if it mixes WATER and ELECTRICITY you need to be very careful.  Please take some time to find out about how and when to use the proper GFCI protection for your application.

CPSC Banner

Consumer Safety About CPSC Library - FOIA Business

Consumer Product Safety Commission

Safety Alert

Install Ground-Fault Circuit-Interrupter Protection for Pools, Spas and Hot Tubs

CPSC Document #5039


The U.S. Consumer Product Safety Commission (CPSC) recommends installing and using ground-fault circuit-interrupters (GFCIs) for protection against electrocution hazards involving electrical circuits and underwater lighting circuits in and around pools, spas, and hot tubs.

CPSC is aware of more than a dozen electrocutions and a similar number of electrical shock incidents involving circuits around swimming pools between 1997 and 2002. Electrical incidents involving underwater pool lighting were more numerous than those involving any other consumer product used in or around pools, spas, and hot tubs.

The greater danger associated with electrical shock in a swimming pool is that anyone in the pool may be rendered immobile and unable to rescue themselves or to call for help. Drowning becomes a likely outcome, even if the current is not immediately lethal. Bystanders and would-be rescuers risk serious injury if the current flow isn’t stopped before they make contact with a conductive fixture, such as a ladder, or enter the water to try to help a victim.

While grounding provides essential protection for pool, spa, and hot tub equipment, GFCIs are the most effective means for protecting people against electrical shock hazards of this nature.

A GFCI constantly monitors the flow of current through a protected lighting fixture, pump motor or appliance circuit and senses any loss of current to an outside path. If the current flowing into an electrical appliance or fixture differs by a very small amount from what flows

back out, the GFCI instantly interrupts the current flow to prevent a sustained, lethal level of electricity from reaching the consumer. The consumer may feel a painful shock but should be protected from electrocution.

The National Electrical Code (NEC) requires GFCI protection for cord- and plug-connected pumps on pools, spas, and hot tubs; 120-volt underwater lighting fixtures; and receptacle outlets in the vicinity of pools, spas and hot tubs. Today, the code prohibits electrical installations closer than five feet from water and requires GFCI protection for all electrical equipment, including 240-volt equipment located five to 10 feet from the water and for receptacles within a 20-foot perimeter.

Older pools, spas and hot tubs may not have adequate GFCI protection. In particular, pools older than 30 years may not have GFCI protection on underwater lighting circuits. Because the NEC provision for spas only became effective in 1981, even somewhat newer spas or hot tubs may not be protected.

CPSC urges consumers to have an electrician who is qualified in pool and spa repairs install adequate GFCI protection for all pool, spa, and hot tub electrical equipment and for underwater swimming pool lighting fixtures. Additionally, outdoor outlets that could potentially be used to plug in electrical appliances (e.g., radios, pumps, washers) used near the pool also should be equipped with GFCI protection. Remember to test the GFCI regularly to be assured of continued protection.

TO PREVENT ELECTROCUTION:

  • Install GFCIs
    • On underwater lighting circuits operating at more than 15 volts.
    • On all electrical equipment used with pools, spas and hot tubs, including heaters operated on 240-volt circuits.
    • On all outdoor receptacles and any indoor receptacles that could potentially be used to power electrical appliances within 20 feet of the water’s edge.
    • In accordance with applicable local codes and the NEC.
  • Test GFCIs monthly to assure continued protection. Infrequently used and portable or cord-connected GFCIs should be tested before each day’s use.
  • To test a GFCI:
    • Plug a nightlight into the outlet and turn it on.
    • Press the “TEST” button. Did the light go out? If not, replace the GFCI.
    • Press the “RESET” button. Did the light come back on? If not, replace the GFCI.
Types of GFCIs

05/14/03

Consumers can obtain this publication and additional publication information from the Publications section of CPSC’s web site or by sending your publication request to info@cpsc.gov.

This document is in the public domain. It may be reproduced without change in part or whole by an individual or organization without permission. If it is reproduced, however, the Commission would appreciate knowing how it is used. Write the U.S. Consumer Product Safety Commission, Office of Information and Public Affairs, 4330 East West Highway, Bethesda, MD 20814 or send an e-mail via CPSC’s On-Line Form.

The U.S. Consumer Product Safety Commission is charged with protecting the public from unreasonable risks of serious injury or death from thousands of types of consumer products under the agency’s jurisdiction. The CPSC is committed to protecting consumers and families from products that pose a fire, electrical, chemical, or mechanical hazard. The CPSC’s work to ensure the safety of consumer products – such as toys, cribs, power tools, cigarette lighters, and household chemicals – contributed significantly to the decline in the rate of deaths and injuries associated with consumer products over the past 30 years.

To report a dangerous product or a product-related injury, call CPSC’s hotline at (800) 638-2772 or CPSC’s teletypewriter at (301) 595-7054, or visit CPSC’s web site at www.cpsc.gov/talk.html. To join a CPSC email subscription list, please go to https://www.cpsc.gov/cpsclist.aspx. Consumers can obtain this release and recall information at CPSC’s Web site at www.cpsc.gov.

Categories: Tip of the Day Tags:

Electrical Tip of the Day: How to wire an outlet (Part I – The WRONG WAY)

March 12th, 2010 artisanchris No comments

What is a number #1 cause of electrical fires in residential occupancies?… failed wire terminations on devices  We see this a lot – typically in older homes with outdated / damaged devices, first generation modern construction homes form the 7o’s, and today in the fast paced new construction track home market.

A friend of mine who recently had this exact issue at his home suggested that we show the correct way to wire an outlet, with an example of the wrong way it can be done and what that might look like.

First – the wrong way.  Here is a picture of an outlet I made up here at the shop to demonstrate a  number of deficiencies and bad practices:

outlet blog - side view - wrong way to wire outlet blog - wrong way to wireIn these two pictures you see a number of issues:

  • (2) ground wires terminated on one screw – each screw on an outlet or switch is to have ONLY ONE WIRE on it
  • Wires that have been stripped back two far that allow exposed conductor to extend from the device
  • STAB IN THE BACK connections – this is a big one, this system is simply a failure waiting to happen.  Don’t use the stab in the back holes on a device!  Most reputable electrical contractors will not use the stab in the back system.  We use a method called “pig tailing” which we will talk about in Part II of this topic
  • Wires landed on a screw that are not properly tightened or terminated – you should not be able to wiggle a wire loose on a device.  Conductors should be bent and trimmed to fit neatly around the screw heads

So there are some examples of the wrong way / things to look for.  IF you see this kind of wiring on an outlet, or wires at a device location that appear to be loose, burnt, cracking. overheated, or otherwise “messy” it is a good idea to get it looked at now.  Fires are really hard to fix later :)

Categories: Tip of the Day Tags:

Electrical Tip of the Day: Careful getting advice from home store Joe!

January 19th, 2010 artisanchris No comments

So recently I was at a local big box home store in the electrical section and overheard a conversation between a homeowner and the guy working the electrical isle.  It went something like this >>>

Homeowner “I am trying to sell my house and was told by the home inspector that it need to have GFCI’s installed”

Big Box Guy “yup – every outlet within 3′ of water – that is a city code now you know”

Homeowner “oh… OK – can you show me how these things wire up”

Big Box Guy “no problem – just put two of the wires here (points) and two of the wires here (points again)”

Homeowner “does it matter which wires go where on this thing?”

Big Box Guy “not really sure, but I think it can wire either way”

Homeowner “thanks, you have been a big help”

So – there are a couple of points I want to make with this weeks tip.

The first one is – don’t automatically trust the advice you get from the home store Joe’s of the world.  In the case above not only was the employee wrong about the code (it’s 6′ and is actually a NEC code) he also instructed the homeowner to wire the device incorrectly (I was standing right there).  This happens all the time  – we get homeowners that get stuck in a pinch, call us to help, then tell us “but the guy at the home store said this was going to be OK”

A second point is – it takes a long time to get a proper education in the trades.  A good combination of an apprenticeship program,  in the field work, and continuing education is a must.  If you do intend to take advise from the home store folks – ask them about their credentials and the source of their knowledge before excepting it as fact.

Here is another example.  I took this picture a few days ago at a local home store.

photo (19)

It is of a big poster display advertising the manufactures product, snap-and-fit ENT (electrical non-metallic tubing).  IMO this stuff is already a pretty low end solution for most applications, and frankly most electrical contractors won’t use it.  The picture shows a junction box with 4 conduits in it – all wired up pretty and ready for the devices to be put in after drywall.  The display is meant to be a an example of how to use the product and it’s install applications. 

HERE IS THE KICKER – the install as pictured has several pretty obvious NEC code violations.  The conduits are not strapped correctly and the box pictured is too small to be used for the application shown.  A box of that size – per 2008 NEC table 314-16(A) – is only permitted to have 9 wires in it – yet the one pictured clearly has 12 or more (I lost count) – and we have not even accounted for the extra room that is required by the NEC for the devices to be installed.  I can only imagine that this same display is up in every one of this chains stores – and yet, no one in the electrical department of any of these stores has noticed that it depicts several code violations?  Way to go home store Joes!

In the end it is your responsibility to make good decisions about your projects and their level of safety and quality – if you have doubts or concerns about electrical installs please feel free to contact me – always happy to help in any way I can.

Categories: Tip of the Day Tags:

Electrical Tip of the Day: Do-it-yourself book recall

January 13th, 2010 artisanchris 1 comment

This just came to me from my Dad, he is a journeymen electrician, electrical inspector, and safety trainer out West.  Just goes to show how much bad information and lack of knowledge is out there in the trades.  Take a look at the recall list below, you have probably noticed these books at the home stores and major booksellers.  If you have question about how to safely do an electrical install at your home or business and do not feel that you are properly trained please contact a qualified electrical contractor.

__________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

U.S. Consumer Product Safety Commission

Office of Information and Public Affairs Washington, DC 20207

FOR IMMEDIATE RELEASE
January 8, 2010
Release # 10-104
Firm’s Recall Hotline: (866) 696-7602
CPSC Recall Hotline: (800) 638-2772
CPSC Media Contact: (301) 504-7908

Home Improvement Books Recalled by Oxmoor House Due to Faulty Wiring Instructions; Shock or Fire Hazard to Consumers

WASHINGTON, D.C. – The U.S. Consumer Product Safety Commission, in cooperation with the firm named below, today announced a voluntary recall of the following products. Consumers should stop using recalled products immediately unless otherwise instructed.

Name of Product: Home Improvement Books

Units: About 951,000

Publisher: Oxmoor House, Inc., of Birmingham, Ala.

Hazard: The books contain errors in the technical diagrams and wiring instructions that could lead consumers to incorrectly install or repair electrical wiring, posing an electrical shock or fire hazard to consumers.

Incidents/Injuries: None reported.

Description: The recall involves nine home improvement books, as listed below:

Title ISBN Publication Date
AmeriSpec Home Repair Handbook 978-0-376-00180-1 January 2006
Lowe’s Complete Home Improvement and Repair 978-0-376-00922-7
978-0-376-01098-8
September 2005
December 1999
Lowe’s Complete Home Wiring 978-0-376-00928-9 May 2008
Sunset Basic Home Repairs 978-0-376-01581-5
978-0-376-01025-4
February 1995
January 1975
Sunset Complete Home Wiring 978-0-376-01594-5 December 1999
Sunset Complete Patio Book 978-0-376-01411-5
978-0-376-01397-2
978-0-376-01399-6
January 2006
January 1998
April 1990
Sunset Home Repair Handbook 978-0-376-01258-6
978-0-376-01256-2
October 1998
February 1985
Sunset Water Gardens 978-0-376-03849-4 January 2004
Sunset You Can Build – Wiring 978-0-376-01596-9 January 2009

Sold at: Home improvement stores and bookstores nationwide from January 1975 through December 2009 for between $13 and $35.

Printed in: United States

Remedy: Consumers should immediately stop using these books and contact Oxmoor House for a full refund.

Consumer Contact: For additional information, contact Oxmoor House toll-free at (866) 696-7602 anytime, or visit the firm’s Web site at www.sunsetrecall.com

Picture of Recalled AmeriSpec Home Repair Handbook Home Improvement Book

Picture of Lowe’s Complete Home Improvement and Repair Recalled Home Improvement Book

Picture of Sunset Basic Home Repairs Recalled Home Improvement Book

Picture of Recalled Sunset Home Repair Handbook Home Improvement Book

Picture of Recalled Lowe’s Complete Home Wiring Home Improvement Book

Picture of Recalled Sunset Complete Home Wiring Home Improvement Book

Picture of Recalled Sunset Water Gardens Home Improvement Book

Picture of Recalled Sunset You Can Build - Wiring Home Improvement Book

Picture of Recalled Sunset Complete Patio Book Home Improvement Book

CPSC is still interested in receiving incident or injury reports that are either directly related to this product recall or involve a different hazard with the same product. Please tell us about it by visiting https://www.cpsc.gov/cgibin/incident.aspx

The U.S. Consumer Product Safety Commission is charged with protecting the public from unreasonable risks of serious injury or death from thousands of types of consumer products under the agency’s jurisdiction. The CPSC is committed to protecting consumers and families from products that pose a fire, electrical, chemical, or mechanical hazard. The CPSC’s work to ensure the safety of consumer products – such as toys, cribs, power tools, cigarette lighters, and household chemicals – contributed significantly to the decline in the rate of deaths and injuries associated with consumer products over the past 30 years.

To report a dangerous product or a product-related injury, call CPSC’s Hotline at (800) 638-2772 or CPSC’s teletypewriter at (301) 595-7054. To join a CPSC e-mail subscription list, please go to https://www.cpsc.gov/cpsclist.aspx. Consumers can obtain recall and general safety information by logging on to CPSC’s Web site at www.cpsc.gov.

Connect with Us!CPSCs OnSafety BlogSee our videos on You TubeFollow us on TwitterSee our pictures on Flickr

Categories: Tip of the Day Tags: